Slendaur Unit
Lawrebce Scott & Electromotors 3.3kv-6.6kv - Slendaur Unit
R&B Switchgear Services Ltd - Switchgear Manufacturers
CompanyServicesProductsWorkshopContact

R&B Switchgear, in recognising our customers needs to support old and obsolete circuit breakers on site, have designed a Vacuum Retrofit (AREVA CLX3) for the 3.3kV / 6.6kV Lawrence, Scott& Electromotors Motor Switching Device.


The retrofit consists of installing a AREVA CLX3 Vacuum Contactor within the existing Lawrence, &Electromotors carriage.

All main interlocks have been retained in the modification to prevent the retrofit being installed or removed from the switchboard whilst in the closed position. By carrying out the retrofit in this way it alleviates the necessity to modify the main switchboard busbars etc. This method, in our opinion is by far the most cost effective solution for upgrading the switchboard on site to guarantee future support and reliability for many years to come.

As part of the Retrofit package, customer’s drawings are updated on CAD to contemporary standards producing standard drawings for each circuit type.
___________________________________________________________________________

Technical Data Vacuum Contactor Type Areva CLX3

Standard:                                                                                                             IEC 60470(2000)
Rated Operational Voltage:                                                                                                   7.2kV
Rated Insulation Voltage:                                                                                                       7.2kV
Rated Frequency:                                                                                                              50/60Hz
Rated Operational Current:                                                                                                    400A
Maximum Fuse Size:                                                                                                               450A
Rated Interrupting Capability Of Fuses:                                                                               43.8kA
Contactor Rated Thermal Current:                                                                                         400A
Contactor Rated Making Capacity BS 775 Cat. AC4 cl.3:                               4.0kA, 7.2kV, 0.23pf
Contactor Rated Breaking Capacity BS 775 Cat. AC4 cl.3:                            3.2kA, 7.2kV, 0.23pf
Contactor Max. Interrupting Capacity:                                                                              4.4/8.8kA
Contactor Short Time Overload Capacity:                                                                    6.0kA 1 sec


Slendaur Unit
DNV

Instrumentation